This product is based on the national standard "JB/T 10738-2007: semi-conductive shielding materials for extruded insulated cables with rated voltages of 35KV and below", the index requirements for peroxide cross-linked semi-conductive shielding materials for ethylene-propylene rubber insulated cable insulation. Production, suitable for cable conductors, long-term allowable cable with a maximum operating temperature of 90 ° C, characterized by excellent processing performance and stable performance.
Serial number | project | unit | HBD | HBD-1 |
Claim | Measured value | Claim | Measured value |
1 | Dense | g/cm3 | ≤1.20 | 1.10 | ≤1.20 | 1.11 |
2 | Tensile Strength | Mpa | ≥6.0 | 7.5 | ≥6.0 | 8.0 |
Elongation at break | % | ≥180 | 260 | ≥200 | 330 |
3 | Hot air aging test | 135±2℃×168h |
Tensile strength change rate ≤ | % | ±30 | 7 | ±30 | 9 |
Breaking elongation change rate ≤ | % | ±30 | -18 | ±30 | -20 |
4 | Impact embrittlement | ℃ | -40 | -45 |
Impact embrittlement performance | Number of failures | ≤15/30 | 10/30 | ≤15/30 | 9/30 |
5 | Heat extension | 0.2Mpa 200±2℃×15min |
Elongation under load | % | ≤80 | 20 | ≤80 | 20 |
Permanent deformation after cooling | % | ≤10 | 6 | ≤10 | 6 |
6 | Volume resistivity at 20 ° C | Ω.cm | ≤100 | 70 | ≤100 | 50 |
7 | Volume resistivity at 90 ° C | Ω.cm | ≤10000 | 5000 | ≤5000 | 2000 |
8 | Volume resistivity after hot air aging | 100±2℃ |
Volume resistivity at 90 ° C | Ω.cm | | | | |
Semi-conductive shielding compound 2019-8-30 本文被閱讀 2638 次