According to GB/T759 4.9-87 standard production; that is, 85~C generally does not extend the rubber sheathing compound. It is used for general cable sheathing of conductors with long-term working temperature of 85~C. It has certain oil/heat/cold/weather resistance and high flame retardancy. It can be used directly as a marine cable sheath and can completely replace chlorine. Butadiene rubber (CR) compound.
Before aging | Tensile strength ≥ | Mpa | 11.0 | 12.7 |
Elongation at break ≥ | % | 300 | 440 |
Air box aging test | Aging condition | temperature | ℃ | 75±2 | 75±2 |
time | | 7×24 | 7×24 |
Tensile strength after aging | ≥ | Mpa | / | / |
Rate of change ≤ | % | -30 | -3 |
Elongation at break after aging | ≥ | % | 200 | 402 |
Rate of change ≤ | % | -40 | -13 |
Thermal extension test | Test conditions | Air temperature | ℃ | 200±3 | 200±3 |
Load time | min | 15 | 15 |
Mechanical stress | N/mm2 | 0.2 | 0.2 |
Elongation under load ≤ | % | 175 | 20 |
Permanent deformation after cooling ≤ | % | 15 | 4 |
Oil immersion test | Test conditions | Oil temperature | ℃ | 100±2 | 100±2 |
Oil immersion test | H | 24 | 24 |
Tensile strength change rate ≤ | % | -40 | -5 |
Elongation at break elongation rate ≤ | % | -40 | -3 |
Marine cable sheathing compound (XH-21A) 2019-8-30 本文被閱讀 2658 次